Understanding Power Requirements: Starting vs Running Wattage
AC units require significantly higher power during startup compared to normal operation.
- Starting Surge: 3-4x higher than running wattage (lasts 2-5 seconds)
- Running Wattage: Continuous power consumption
Example:
- 1 Ton AC: 2,500–3,000W (start), 1,200–1,800W (run)
- 1.5 Ton AC: 3,500–4,500W (start), 1,500–2,000W (run)
Key Tip: Always size generator based on starting surge, not running power.
Generator Sizing Guide
| AC Type | Minimum Generator | Recommended |
|---|---|---|
| 1 Ton (Inverter) | 2.5 KVA | 3 KVA |
| 1 Ton (Non-Inverter) | 3.5 KVA | 4 KVA |
| 1.5 Ton (Inverter) | 3.5 KVA | 4 KVA |
| 1.5 Ton (Non-Inverter) | 5 KVA | 5.5–6 KVA |
Generator vs IPS: Which is Better?
- IPS: Suitable only for small loads (lights, fans)
- Generator: Best for AC usage and long outages
Conclusion: For Bangladesh homes, generators are more practical than IPS for AC backup.
Why Voltage Stabilizer is Essential
Voltage fluctuations (180V–250V) in Bangladesh can damage AC compressors.
- Prevents voltage spikes
- Protects compressor
- Costs ৳3,000–8,000 but saves ৳30,000+ repair
Step-by-Step Safe Setup
- Start generator and wait 3-5 minutes
- Connect voltage stabilizer
- Turn off all other appliances
- Switch on AC
- Add other loads gradually
Common Mistakes to Avoid
- Using undersized generator
- Skipping stabilizer
- Running multiple appliances at startup
- Switching power without turning AC off
- Using IPS for non-inverter AC
Safety Tips
- Always place generator outdoors
- Ensure proper grounding
- Monitor fuel levels
- Never overload generator
Recommended Products
- 4–5 KVA Generator
- 5 KVA Voltage Stabilizer
- Inverter AC (energy efficient)
Conclusion
Running AC on generator or IPS in Bangladesh is safe only when done correctly. Proper generator sizing, voltage stabilization, and safe switching methods prevent costly damage and ensure uninterrupted cooling during power outages.